www.lakemonitors.comProduct ManualFor Lake Flow Meters,Alarms and Transmitters

Strona 2 - TABLE OF CONTENTS

The indicated flow reading will read high for heavier fluids and low forlighter fluids. A corrective factor can be applied to the standard scaleor a s

Strona 3 - FLOW METERS

Measuring ranges cover 1.5-12 SCFM through 150-1300 SCFM.Twenty-four port sizes from 1/8" through 2" in NPT, SAE and BSP canbe ordered to me

Strona 4 - Specifications

DENSITY CORRECTION FACTORSSCFM (indicated) x (CF) = SCFM (Actual) CF = (f1) x (f2) X (f3)Note: all correction factors need not be used.Table 1. (f1)

Strona 5

Page 13 / Flow Meters / Lake ManualSelecting the Proper MetersTo order a pneumatic flow meter the following information is required:n pipe size and po

Strona 6 - INSTALLATION

TROUBLESHOOTING & MAINTENANCEPage 14 / Flow Meters / Lake ManualTROUBLESHOOTING CHARTMalfunction: Magnet follower sticks in mid-scale and will not

Strona 7

Page 15 / Flow Meters / Lake ManualTROUBLESHOOTING CHART (CONTINUED)Malfunction: Window tube is cracking or crazing.Possible Cause:Using incompatible

Strona 8 - OPERATION

DisassemblyImportant: It is not necessary to remove window tube or window seals to clean the meter. Note also how the meterdisassembles for easy of re

Strona 9 - Reading the Meter

IMPORTANT: If inner cartridge does not slide out freely, it may be sign of contamination. The transfer magnet is a powerful ALNICO magnet. Keep it awa

Strona 10 - Viscosity Effect

Cleaning and InspectionNote: If the inner cartridge is damaged or contaminated beyond repair, the complete meter can be sent to the manufacturer for e

Strona 11

FILTRATION AND CONTAMINATIONRecommended FiltrationThe manufacturer recommends system filtration of at least 74 micronfilter or a 200 mesh screen. It h

Strona 12 - DENSITY CORRECTION FACTORS

This manual is a service guide produced by Lake Monitors andprovides specific procedures and/or illustrations for disassembly,assembly, inspection, cl

Strona 13

Self-Generation ContaminationSelf-generated contamination is a product of wear, cavitation,fluid breakdown and corrosion. Systems that are carefully f

Strona 14 - TROUBLESHOOTING CHART

FLOW ALARMSwww.lakemonitors.com

Strona 15

NOTE: Installation, operation and cleaning instructions for the basic flow metercartridge can be found in the first section of this manual. The follow

Strona 16 - Disassembly

The pointer indicates the set point for the alarm switch. In Illustration1, the switch will be actuated at all flow rates below 4 GPM. Tochange the se

Strona 17

Switches SpecificationsType Form C, dry contactUL/CSA Rating 10 & 1/4 hp, 125 or 250 VAC1/2 A, 125 VDC & 1/4A, 250 VDC3A, 125 VAC “L” lamp loa

Strona 18 - Cleaning and Inspection

Illustration 7 shows the connections for a standard, single switchFlow Alarm as they are shipped from the factory. The wiring for othertypes of connec

Strona 19 - FILTRATION AND CONTAMINATION

Standard Control CircuitsPage 26 / Flow Alarms / Lake Manual

Strona 20 - Basic Application Information

Page 27 / Flow Alarms / Lake Manual* The load must be within the flow alarm’s and the slave relay’s contact rating. Please see specifications.

Strona 21 - FLOW ALARMS

NOTES: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Strona 22 - Overview

FLOWTRANSMITTERSwww.lakemonitors.com

Strona 23 - Switches

www.lakemonitors.comFLOW METERS

Strona 24 - Electrical Connections

NOTE: Installation, operation and cleaning instructions for the basic flow metercartridge can be found in the first section of this manual. The follow

Strona 25 - Illustration 7

The sensor array located in the sensor assembly sends a signalrelative to the position of the follower to the signal conditioning circuit.The signal c

Strona 26 - Standard Control Circuits

4-20 mA Output ConnectionsWiring Instructions (Refer to Illustrations 2 and 3 above):1) Move the programmable jumper on the signal conditioningboard i

Strona 27

0-5 VDC Output ConnectionsWiring Instructions (Refer to Illustrations 4 and 5 above):1) Move the programmable jumper on the circuit board into theposi

Strona 28

0-2000 Hz Pulse Output ConnectionsWiring Instructions (Refer to Illustrations 6 and 7 above):1) Move the programmable jumper on the circuit board into

Strona 29 - TRANSMITTERS

1-5 VDC Output ConnectionsWiring Instructions (Refer to Illustrations 8 and 9 above):1) Move the programmable jumper on the signal conditioning board

Strona 30

ConnectorsStandard flow sensors are prewired with 4-wire Hirschmann-type DINconnectors which consist of a male section as shown in Illustration 10and

Strona 31

User AdjustmentsThe 4-20 mA, 0-5V, and 0-2000 Hz square wave outputs on the LakeMonitors Flow Transmitter are all factory calibrated. User adjustments

Strona 32 - 4-20 mA Output Connections

12) Gradually increase the flow through the system until the flow rate indicated on the printed flow rate scale reaches full-scale (the highest value

Strona 33 - 0-5 VDC Output Connections

NOTES: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Strona 34 - Illustration 6 Illustration 7

Basic Application InformationThe flow meter can be installed directly in the fluid line without flowstraighteners or special piping. The meter is used

Strona 35 - 1-5 VDC Output Connections

For downloadable product manuals,data sheets and CAD drawings,visit Lake’s web site today!www.lakemonitors.comLAKE MONITORS 8809 INDUSTRIAL DRIVE, F

Strona 36 - Connectors

Warning and Precautionary Areas1) The meters are designed to operate in systems that flow in only one direction: the direction of the arrow on the flo

Strona 37 - User Adjustments

INSTALLATIONBasic Installation InstructionsThe meters are mounted in-line and are direct reading. The meterscan be mounted in a vertical or horizontal

Strona 38 - Trouble Shooting

Fluid Flow in Reverse DirectionThe standard meter will not permit flow in the reverse direction(opposite direction to the arrow printed on the flow ra

Strona 39

OPERATIONOperating PrinciplesLake has developed a line of unique flow meters which combine thesimplicity of a sharp-edged orifice disk and a variable

Strona 40

1. End Porting 8. Flowing Sharp-Edged Orifice Disk2. Body Casing 9. Tapered Center Shaft3. Magnet Follower 10. Transfer Magnet4. Window Tube 11. Scale